Toho-electronics TTM000 Instrukcja Użytkownika Strona 21

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 42
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 20
21
6.3 Composition of an RTU request message (transmitted from a high-level computer
to this product)
For codes a) through i), see "6.5 Description of RTU codes."
6.3.1 Composition of a read request message
a)
Slave address
1BH
b)
Function code
03H
c)
Register address
High level
00H
First register address
Low level
00H
d)
Number of registers
High level
00H
Fixed at 2
Low level
02H
e)
CRC-16
Low
level
31
H
High
level
C6
H
6.3.2 Composition of a write request message
a)
Slave address
03H
b)
Function code
10H
c)
Register address
High level
00H
First register address
Low level
C0H
d)
Number of registers
High level
00H
Fixed at 2
Low level
02H
f)
Number of data items
04H
Number of registers
2
g)
Data for the first register
(a low-level word)
High level
00H
When writing
,
,
, and
H in the data, write them in the
order described on the left-hand
side. ( represents 1 byte.)
Low level
6FH
Data for the first register + 1
(a high-level word)
High level
00H
Low level
00H
e)
CRC-16
Low
leve
l
5A
H
High
level
C4
H
6.3.3 Composition of a store request message
a)
Slave address
03H
b)
Function code
10H
c)
Register address
High level
02H
First register address
Low level
0EH
d)
Number of registers
High level
00H
Fixed at 2
Low lev
el
02H
f)
Number of data items
04H
Number of registers
2
g)
Data for the first register
(a low-level word)
High level
00H
The data about the storage of settings is
arbitrary.
Low level
00H
Data for the first register + 1
(a high-level word)
Hi
gh level
00H
Low level
00H
e)
CRC-16
Low
level
FB
H
High
level
60
H
Przeglądanie stron 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 41 42

Komentarze do niniejszej Instrukcji

Brak uwag