5.6 Common parameter setting mode SET 5 to 8
SET05 to SET08
Name
Setting content
Initial value
1
E*F1
Event function 1 setting
Function
Add-on function
00
*0
None
0*
None
*1
Deviation upper and lower limits
1*
Hold
*2
Deviation upper limit
2*
Standby
*3
Deviation lower limit
3*
Delay
*4
Deviation range
4*
Hold + standby
*5
Absolute value upper and lower limits
5*
Hold + Delay
*6
Absolute value upper limit
6*
Standby + Delay
*7
Absolute value lower limit
7*
Hold + standby + Delay
*8
Absolute value range
2
E*H
Event upper limit setting
Thermocouple/RTD input -1999.9 to 2999.9 (C) -1999 to 2999 (C) Note that for
R, B and PR40-20 of thermocouple, the following is to be applied. -1999 to 9999 (C)
0
Current/voltage input -19999 to 29999 (digit)
3
E*L
Event lower limit setting
Thermocouple/RTD input -1999.9 to 2999.9 (C) -1999 to 2999 (C) Note that for
R, B and PR40-20 of thermocouple, the following is to be applied. -1999 to 9999 (C)
0
Current/voltage input -19999 to 29999 (digit)
4
E*C
Event sensitivity setting
Thermocouple/RTD input 0.0 to 999.9 (C) 0 to 999 (C)
0
Current/voltage input 0 to 9999 (digit)
5
E*T
Event Delay timer setting
0 to 9999 (second)
0
6
E*F2
Event function 2 setting
(loop abnormality)
Function
Add-on function
00
*0
Nonexistent
0*
None
*1
Existent
1*
Hold
7
E*P
Event polarity setting
0
Normal open
1
Normal close
0
5.7 Common parameter setting mode SET 9 (1)
SET09
Name
Setting content
Initial value
1
MLF
Operation amount function
setting
0
None
2
Operation amount current limiter(average)
0
1
Operation amount limiter
3
Operation amount current limiter(R.M.S)
With the selection of [MLF =1], the following 2 to 9 are selectable for [CNT =1]; the following 2 to 17 are selectable for [CNT = 3 or 4].
* Below, 2 and 3 are for the operation amount limiter function setting, i.e., effective when 1 is selected.
2
MLH11
Primary control operation amount limiter upper limit 1
MLL11 to 100.0(%)
100.0
3
MLL11
Primary control operation amount limiter lower limit 1
0.0 to MLH11(%)
0.0
* Below, 4 and 5 are for the operation amount limiter function setting, i.e., effective when 2 is selected.
4
MLH21
Primary control operation amount limiter upper limit 2
MLL21 to 100.0(%)
100.0
5
MLL21
Primary control operation amount limiter lower limit 2
0.0 to MLH21(%)
0.0
* Below, 6 and 7 are for the operation amount limiter function setting, i.e., effective when 3 is selected.
6
MLH31
Primary control operation amount limiter upper limit 3
MLL31 to 100.0(%)
100.0
7
MLL31
Primary control operation amount limiter lower limit 3
0.0 to MLH31(%)
0.0
* Below, 8 and 9 are for the operation amount limiter function setting, i.e., effective when 4 is selected.
8
MLH41
Primary control operation amount limiter upper limit 4
MLL41 to 100.0(%)
100.0
9
MLL41
Primary control operation amount limiter lower limit 4
0.0 to MLH41(%)
0.0
* Below, 10 and 11 are for the operation amount limiter function setting, i.e., effective when 1 is selected.
10
MLH12
Secondary control operation amount limiter upper limit 1
MLL12 to 100.0(%)
100.0
11
MLL12
Secondary control operation amount limiter lower limit 1
0.0 to MLH12(%)
0.0
* Below, 12 and 13 are for the operation amount limiter function setting, i.e., effective when 2 is selected.
12
MLH22
Secondary control operation amount limiter upper limit 2
MLL22 to 100.0(%)
100.0
13
MLL22
Secondary control operation amount limiter lower limit 2
0.0 to MLH22(%)
0.0
* Below, 14 and 15 are for the operation amount limiter function setting, i.e., effective when 3 is selected.
14
MLH32
Secondary control operation amount limiter upper limit 3
MLL32 to 100.0(%)
100.0
15
MLL32
Secondary control operation amount limiter lower limit 3
0.0MLH32(%)
0.0
* Below, 16 and 17 are for the operation amount limiter function setting, i.e., effective when 4 is selected.
16
MLH42
Secondary control operation amount limiter upper limit 4
MLL42 to 100.0(%)
100.0
17
MLL42
Secondary control operation amount limiter lower limit 4
0.0 to MLH42(%)
0.0