13
Monitor window parameters
a) Identifier
b) Name c) R/W d) Description and set range e) Remark
PV1 Measurement R Used as a measurement monitor
When over-scale: HHHHH (the same is true when the
sensor has a wire break)
When under-scale: LLLLL
CM*
*: 1 to 8
CT measurement R R of the measured current of the heater current
detector
When over-scale: HHHHH
When reading is impossible: -----
When reading is
impossible: The CT
value cannot be read
unless the output of no
less than 190mS is
turned on.
DIM DI monitor R R of the voltage input monitoring
00000: State where voltage input is not applied
00001: State where voltage input is applied
OM1 Monitor the control output R R of the control output monitoring
000①②
Output 1 state 1:ON/0:OFF
Output 2 state 1:ON/0:OFF
*2
EM1 Monitor the temperature
alarm outputs 1 to 4
R R of the temperature alarm output monitoring
0①②③④
: temperature alarm output 4
: temperature alarm output 3
: temperature alarm output 2
: temperature alarm output 1
*3
EM2 Monitor the temperature
alarm outputs 5 to 8
R R of the temperature alarm output monitoring
0①②③④
: temperature alarm output 8
: temperature alarm output 7
: temperature alarm output 6
: temperature alarm output 5
*3
ALM Monitor the alarm output R R of the alarm monitoring
00①②③
Alarm output of heater wire break (1:ON/0:OFF)
Alarm output of SSR breakdown (1:ON/0:OFF)
Error alarm output (1:ON/0:OFF)